1X Technologies SuperNuclear High-Temperature Tray Cable
SuperNuclear – UL Type TC/TC-ER and cUL CIC TC-ER
600V Power & Control Tray Cable – Class 1 Div 2 Hazardous Areas
Conductor/90°C Wet or Dry, Non-UL 105C+, 90C/130C/250C
For Cable Tray Use – Sunlight Resistant – For Direct Burial
SuperNuclear Cable Insulation:
Nuclear Grade Heat, moisture, flame, and chemical resistant, mechanically rugged ethylene-propylene insulating compound. The properties of the ferromagnetic resonance substantially enhances the well-known features of ethylene-propylene rubber insulations.
SuperNuclear Cable Overall Jacket:
Hard Usage, Rugged PVC jacket is mechanically rugged and has excellent resistance to most chemicals, is sunlight resistant, and passes (UL) Vertical Flame Tests.
SuperNuclear Cable Applications:
SuperNuclear TC-ER tray cable is permitted for use on power, lighting, control, and signal circuits; indoors or outdoors; in cable trays, raceways, direct burial in the ground, or where supported in outdoor locations by a messenger wire; for Class 1 circuits as permitted in Article 725 of the NEC; and in cable trays in Class I, Division 2 hazardous locations in industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons will service the installation. Cables marked TC-ER may also be used between a cable tray and the utilization equipment or device when installed in accordance with the NEC.
SuperNuclear Cable Specifications
SuperNuclear Conductors:
Uncoated soft copper per ASTM B-3. Sizes smaller than #8 are compress stranded per ASTM B-8. Sizes #8 and larger are compact stranded per ASTM B-496.
SuperNuclear Insulation:
Nuclear Grade meets or exceeds requirements of UL 1581, ICEA S-73-532 (NEMA WC57) and ICEA S-95-658 NEMA WC70 Type II insulation.
SuperNuclear Color Coding:
Contact us for Colors Data Sheet. For sizes #8 AWG and larger black conductors with surface printing of numbers per ICEA S-73-532 NEMA/WC57 Method 4.
SuperNuclear Grounding Conductor:
Where indicated, bare stranded copper per ASTM B-8, or compact round per ASTM B-496, Class B & NEC Table 250.122.
SuperNuclear Assembly:
Conductors cabled in accordance with UL 1277 and 1309 using fillers, as necessary, with a cable tape overall.
SuperNuclear Overall Jacket:
Complies with UL 1277 and 1309. The Nuclear Grade compound meets or exceeds the requirements of UL 1581. UL Listed as Type TC or TC-ER cable with a sunlight resistant low-temperature jacket and for direct burial. Sizes 4 AWG and larger without a grounding conductor are Type TC only (not ER).
SuperNuclear Cable Features:
Insulated conductors are UL rated VW-1. 90°C continuous rating in wet or dry 130°C emergency overload rating 250°C short circuit rating. SuperNuclear Type TC-ER are quality control inspected to meet or exceed applicable industry standards. Resistant to moisture and most chemical atmospheres. Thermal stability at elevated temperatures, and High-Temperatures. Flexible, easy to install and terminate. High dielectric strength. Installation Temperature -40°C.
SuperNuclear Applicable Industry Standards:
UL listed for cable tray use, direct burial, in ducts, and sunlight resistant. • Vertical Tray Flame Tests; IEEE 383-1974, FT4/IEEE 1202, UL 1277, Sizes 250 kcmil and larger meet ICEA T-29-520 (210,000 BTU/hr). • OSHA Acceptable • UL certified to IEEE 1580 – Marine Shipboard Cable rated 600/1000V. • ABS Type approved; API-RP-14F, IEEE 45 & 1202, 46 CFR 111.60. • CSA C22.2 No. 239 Type CIC for sizes 4/0 AWG and smaller. • CSA C22.2 No. 230 Type TC-ER for sizes 4/0 AWG and smaller. • 1000V CSA Type CIC available for sizes 4/0 AWG and smaller.
SuperNuclear High-Temperature Tray Cable
Conductor Size AWG (strands) | Number of Conductors | Insulation Thickness-mils | Jacket Thickness-mils | Approx. O.D.-Inches | Approx. Net Wt (lbs/M’) |
---|---|---|---|---|---|
14(7x) | 3 | 30 | 45 | 0.40 | 104 |
14(7x) | 4 | 30 | 45 | 0.44 | 126 |
14(7x) | 5 | 30 | 45 | 0.48 | 151 |
14(7x) | 7 | 30 | 45 | 0.52 | 195 |
14(7x) | 12 | 30 | 60 | 0.71 | 332 |
14(7x) | 19 | 30 | 60 | 0.82 | 480 |
14(7x) | 37 | 30 | 80 | 1.14 | 925 |
12(7x) | 3 | 30 | 45 | 0.44 | 134 |
12(7x) | 4 | 30 | 45 | 0.48 | 167 |
12(7x) | 5 | 30 | 45 | 0.52 | 202 |
12(7x) | 7 | 30 | 60 | 0.60 | 281 |
12(7x) | 9 | 30 | 60 | 0.70 | 363 |
12(7x) | 12 | 30 | 60 | 0.78 | 446 |
12(7x) | 19 | 30 | 80 | 0.95 | 697 |
10(7x) | 3 | 30 | 45 | 0.49 | 183 |
10(7x) | 4 | 30 | 60 | 0.57 | 243 |
POWER CABLES
Conductor Size AWG/kcmil (strands) | Number of Phase Conductors | Insulation Thickness-mils | Jacket Thickness-mils | Approx. O.D.-Inches | Approx. Net Wt (lbs/M’) |
---|---|---|---|---|---|
12(7x) | 3 | 12 (2) | 30 | 0.48 | 162 |
10(7x) | 3 | 10 (2) | 30 | 0.62 | 223 |
8(7x) | 3 | 10 (2) | 45 | 0.72 | 332 |
6(7x) | 3 | 8 (2) | 45 | 0.80 | 482 |
4(7x) | 3 | 8 (2) | 45 | 0.82 | 703 |
2(7x) | 3 | 6 (3) | 45 | 0.99 | 997 |
1/0(7x) | 3 | 6 (3) | 55 | 1.18 | 1469 |
2/0(7x) | 3 | 6 (3) | 55 | 1.26 | 1819 |
4/0(7x) | 3 | 4 (3) | 55 | 1.48 | 2646 |
350(7x) | 3 | 3 (3) | 65 | 1.88 | 4301 |
500(7x) | 3 | 2 (3) | 65 | 2.14 | 5909 |